Must Online UPS 10KVA 10KW EH5500-H10K
Contact support
Pick a department — the chat opens with the product name and link ready.
MUST High Frequency Single Phase Online UPS EH5500-H10K
Performance:
• With double conversion online design, zero output transfer time.
• Adopt DSP digital control, excellent performance indicators, more steady and reliable.
• Adopt active power factor correction technology (PFC), the input power factor is 1, can reduced the pollution to the grid, to energy saving and reducing system investment cost.
• Ultra-wide input voltage range , input voltages available 110V instead of turn to battery power.
• With LCD+LED real-time display, UPS operating available for Detection
• With self- detection function, can detect hidden faults of UPS
• Cold start by battery without grid Input.
• Input frequency range 40~70Hz, support various fuel generators
• With AC input over voltage, low voltage protection, output overload protection, short circuit protection, temperature protection, battery low voltage warning protectionand battery overcharge protection.
• Output power factor 1.0 for your option. max efficiency reach 95%, reduce loss of UPS.
• With input neutral and live line detection function, avoid the reverse connection of UPS utility input
• When utility cut-off, the UPS discharge battery in the battery mode; when the city power is recovery ,UPS turn on automatically,and charge battery at the same time, asunattended function.
• Standard RS232 communication outlet ,connect UPS and computer to realize multifunctional and multi-purpose monitoring and management operations, available SNMP card (optional) to UPS remote monitoring function.
• With 3-5 minutes can work when on full loads.
Specification
MODEL
H10K
Capacity
Rated Capacity
10KVA/10KW
PF
1
Input
Input format
L+N+PE
Rated input voltage
208/220/230/240VAC
Voltage range
110~300VAC
Frequency range
50/60±6Hz (Default), ±10Hz (Settable)
Input power factor
≥0.99
Input total harmonic distortion
≤4% inear load
Output
Output format
L+N+PE
Output voltage
208/220/230/240VAC
Output accuracy
±1%
Output frequency
For on-line mode: follow current frequency, battery mode: 50 / 60Hz±0.1%
Output harmonic distortion
≤ 2% linear load; ≤ 4% nonlinear load (PF=0.7)
Overload capacity
AC Mode:
30min@102%~110% Load;
10min@110%~130% Load;
30s@130%~150% Load;
200ms@>150% Load
Battery Mode:
10min@102%~110% Load;
1min@110%~130% Load;
10s@130%~150% Load;
200ms@>150% Load
Switching time
Switch to battery mode
0ms
Switch to bypass
4ms
AC priority mode
Support
Efficiency
AC Mode (Full Load)
Peak efficiency 95.5%,Full load efficiency 95%
Battery Mode (Full Load)
Peak efficiency 95.3%,Full load efficiency 94.8% (20pcs Battery)
Battery
Battery type
Lead Acid Battery
Battery number
9Ah*16
Chaging current
1A (default)
Charging mode
Two-stage/three-stage charging
Display
LCD
2×8 PIN/Pitch 2.54mm, support 128-bit segment code, up to 4 buttons + 4 LEDs, can display operating mode / load / input / output, etc.
Interface
RS-232
Support: Windows 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC
USB
Windows Family & MAC
EPO
Support
Intelligent slot (Optional)
SNMP/AS400 Relay Card/RS485
Maintenance bypass switch (Optional)
Support
Environmental parameters
Operating ambient temperature
0~40℃
Operating environment humidity
20%~95%(no condensation)
Storage temperature
-15~60℃ (batteries: 0~40℃ )
Altitude
The elevation should not exceed 1000m, 1000m or above, up to 4000 m, reference IEC62040
Noise
≤ 45db
Mechanical Specifications
Dimensions (D*W*H) (mm)
500*250*615
Net weight (kg)
55