  • Model: GXK-3-3-40-IE
  • Capacity: 40kVA / 36kW
  • Topology: Online Double Conversion with DSP Control
  • Parallel Operation: N+X Redundancy, up to 4 units in parallel
  • Input Voltage: 380/400/415Vac (3Ph + N + PE)
  • Input Voltage Range: 305–478Vac at Full Load / 208–478Vac at 50% Load
  • Input Frequency: 40–70Hz (50/60Hz Auto-Sensing)
  • Input Power Factor: ≥0.99
  • Input THDi: ≤3% with Linear Load
  • Bypass Voltage: 220/230/240Vac with selectable voltage tolerance
  • Bypass Frequency Protection: 50/60Hz ±10%
  • ECO Mode: Supported
  • Generator Compatible: Yes
  • Output Voltage: 380/400/415Vac (3Ph + N + PE)
  • Output Frequency: 50/60Hz ±0.1% in Battery Mode
  • Output Waveform: Pure Sinewave
  • Transfer Time: 0ms AC to Battery / 0ms Inverter to Bypass
  • Efficiency: Up to 94.5%
  • Battery Voltage: ±180Vdc Standard
  • Battery Configuration: 2 × 30 × 12V 9Ah; 7Ah optional
  • Long-Run Battery Voltage: ±180 to ±300Vdc
  • Battery Quantity: 30–50 batteries depending on configuration
  • Charging Current: 2.7A Standard / Up to 20A for Long Run Unit
  • Display: 2.4-inch TFT LCD; 7-inch LCD optional
  • Communication: RS232 / RS485 / Parallel Port / Dry Contact / Intelligent Slot
  • Network Management: SNMP Card (Optional)
  • Other Options: Relay Card / Battery Temperature Sensor / Dual Input Source
  • Protection: Short Circuit, Overload, Overheat, Battery Overcharge & Overdischarge, Output Low Voltage, Fan Fault
  • Operating Temperature: 0–40°C
  • Noise Level: <64dB
  • Dimensions: 250 × 900 × 868 mm (Standard Unit)
  • Weight: 239 kg (with 2 × 30 × 9Ah batteries)
UPS GETX 40KV 3PH Online GXK-3-3-40-IE 9,000,000